The measuring instrument provides the following specifications:
- Scattered light measuring principle
- Optional sample air heater for fog compensation
- Measuring ranges: 0..0.05 Em-1, 0.1 Em-1, 0..1 Em-1
- Resolution: 0.001 Em-1
- Integrated temperature sensor for localisation of the fire
- T90 response time: 5 s
- No moveable components
- Simple wall or ceiling mounting
- Ambient temperature –30..+55 °C
- Protection IP65
- Protected against aggressive atmosphere
- Simple calibration check with checking rod
- Signal output via 2 digital coded relay contacts (alarm)
- Optional signal output via Profibus DP
- Programming via Profibus DP or handheld control unit
- Power supply 85..264 V / 47..440 Hz